A small town with a demand of 800 kW of electric power at 220 V is situated 15 km away from an electric plant generating power at 440 V. The resistance of the two line wires carrying power is 0.5Ω per km. The town gets power from the lines through a 4000-220 V step down transformer at a substation in the town.
Estimate the line power loss in the form of heat.
(b) How much power must the plant supply. assuming there is negligible power loss due to leakage?
(c) Characterize the step up transformer at the plant.
400 kW
600 kW
300 kW
800 W
The correct Answer is:B
To solve the problem step by step, we will break it down into parts as follows:
Part (a): Estimate the line power loss in the form of heat.
1. Calculate the total resistance of the transmission line:
- The resistance of the line is given as 0.5Ω/km.
- The distance from the plant to the town is 15km.
- Total resistance R can be calculated as:
R=Resistance per km×Distance=0.5Ω/km×15km=7.5Ω
2. Calculate the output current at the town:
- The power demand of the town is 800kW at 220V.
- The output current I can be calculated using the formula:
I=PV=800×103W220V≈3636.36A
3. Calculate the power loss in the transmission line:
- The power loss Ploss in the line can be calculated using:
Ploss=I2R
- Substituting the values:
Ploss=(3636.36A)2×7.5Ω≈100,000,000W=100kW
Part (b): How much power must the plant supply?
1. Calculate the total power supplied by the plant:
- The total power supplied by the plant Ptotal is the sum of the power demand and the power loss:
Ptotal=Pdemand+Ploss=800kW+100kW=900kW
Part (c): Characterize the step-up transformer at the plant.
1. Calculate the voltage drop across the line:
- The voltage drop Vdrop can be calculated using:
Vdrop=I×R=3636.36A×7.5Ω≈27,272.73V
2. Determine the primary and secondary voltages:
- The primary voltage at the plant is 440V.
- The secondary voltage after the transformer can be calculated as:
Vsecondary=Vprimary+Vdrop=440V+27,272.73V≈27,712.73V
3. Characterize the transformer:
- The transformer is characterized by its input and output voltages:
- Input voltage: 440V
- Output voltage: 27,712.73V
Summary of Results:
- (a) Line power loss: 100kW
- (b) Total power supplied by the plant: 900kW
- (c) Transformer characterization: 440V→27,712.73V
- The resistance of the line is given as 0.5Ω/km.
- The distance from the plant to the town is 15km.
- Total resistance R can be calculated as:
R=Resistance per km×Distance=0.5Ω/km×15km=7.5Ω
- The power demand of the town is 800kW at 220V.
- The output current I can be calculated using the formula:
I=PV=800×103W220V≈3636.36A
- The power loss Ploss in the line can be calculated using:
Ploss=I2R
- Substituting the values:
Ploss=(3636.36A)2×7.5Ω≈100,000,000W=100kW
- The total power supplied by the plant Ptotal is the sum of the power demand and the power loss:
Ptotal=Pdemand+Ploss=800kW+100kW=900kW
- The voltage drop Vdrop can be calculated using:
Vdrop=I×R=3636.36A×7.5Ω≈27,272.73V
- The primary voltage at the plant is 440V.
- The secondary voltage after the transformer can be calculated as:
Vsecondary=Vprimary+Vdrop=440V+27,272.73V≈27,712.73V
- The transformer is characterized by its input and output voltages:
- Input voltage: 440V
- Output voltage: 27,712.73V
- (a) Line power loss: 100kW
- (b) Total power supplied by the plant: 900kW
- (c) Transformer characterization: 440V→27,712.73V
Topper's Solved these Questions
Similar Questions
A town situated 20 kW away from a power plant generating power at 440 V requires 600 KW of electric power at 200 V. The resistance of two wire lines carrying poweris 0.4Ω per km. The town gets power from the line through a 3000-220 V step down transformer at a substation in the town. Find line power losses in the form of heat. How much power must the plant supply assuming that there is negligilbe power loss due to leakage ?
View Solution(a) Draw the diagram of a device which is used to decrease high S voltage into a AC voltage and state its working principle. Write four sources of energy loss in this device.
(b) A small town with a demand of 1200 kW of electric power at 220 V is situated 20 Km away from an electric plant generating power at 440V. The resistance of the two wire line carrying power is 0.5Ω per km. The town gets the power from the line through a 4000-220 V step-down transformer at s sub-station in the town. Estimate the line power loss in the from of heat.View SolutionAn electric iron is rated at 220 V, 2 kW.
Why is the fuse absolutely necessary in a power circuit?View SolutionA power transmission line feeds input power at 2200 V to a step-down transformer with its primary windings having 3000 turns. Find the number of turns in the secondary to get the power output at 220V.
View SolutionAn electrical power line, having a total resistance of 2Ω, delivers 1kW at 220 V. The efficiency of the transmission line is approximately :
View SolutionA cable of resistance 10Ω carries electric power from a generator producing 250kWat10,000V. The current in the cable is
View SolutionAn electric bulb is designed to draw P0 power at V0 voltage. If the voltage is V, it drawas power. Then
View SolutionTwo cities are 150km apart. Electric power is sent from one city to another city through copper wire. The fall of potential per km is 8V and the average resistance per km is 0.5Ω. The power loss in the wire is
View SolutionTwo cities are 80km apart . The electric power is sent from one City to another city through copper wires . The fall of potential per km is 8V and average resistance per km is 0.25ω . The power loss in wire is
View SolutionTwo cities are 80 km apart. The electric power is sent from one city to another city through copper wires. The fall in potential per km is 8 V and average resistance per km is (0.25Ω). The power loss in wire is
View Solution